In a data centre, a rack of computer servers is submerged in a tank of a coolant liquid that boils at 49 ∘C. The vapour condenses on coils at the top of the tank, which are cooled by water flowing through them, and drips back into the tank.
The servers operate from a 48 V supply and draw a total current of 255 A. All the electrical energy is transferred to the coolant as thermal energy.
mass of coolant = 75 kg
specific heat capacity of coolant = 1100 J kg−1K−1
specific latent heat of vaporisation of coolant = 1.0×105 J kg−1
specific heat capacity of water = 4200 J kg−1K−1
(a) Show that the rate of energy transfer to the coolant is about 12 kW. (2)
(b)
(i) The coolant is at 22 ∘C when the servers are switched on. Calculate the time taken for it to reach its boiling point. (2)
(ii) Suggest why the actual time is longer than your answer to (b)(i). (1)
(c) Calculate the mass of coolant vaporised each minute once the coolant is boiling. (2)
(d) Explain why a coolant that boils is more effective at removing energy from the servers than the same mass of a coolant that only warms up by 10 K. (2)
(e) The cooling water enters the coils at 18 ∘C and leaves at 26 ∘C. Calculate the minimum mass of water that must flow through the coils each second. (3)